MODEL |
10K(L)* |
20K(L)* |
30K(L) |
40K(L) |
|
|
PHASE |
3Ph in/ 3Phout or3Ph in1Ph out or1Ph in1Ph out |
3-phasein/3-phaseout |
|||
|
CAPACITY |
10KVA /10KW |
20KVA /20KW |
30KVA /30KW |
40KVA /40KW |
|
|
PARALLEL CAPABILITY |
4 |
||||
|
INPUT |
|||||
|
Nominal Voltage |
3x400VAC(3Ph+N)/230VAC (1Ph+N) |
3x360/380/400/415VAC(3Ph+N) |
|||
|
VoltageRange |
110-300VAC±3%@50%load;176-276VAC±3%@100%load |
||||
|
FrequencyRange |
46~54 Hz or56~64Hz |
40~70Hz |
|||
|
PowerFactor |
≧0.99@100%Load |
||||
|
Harmonic Distortion (THDi) |
<4%at fulllinear load |
||||
|
OUTPUT |
|||||
|
OutputVoltage |
3x360/380/400/415VAC(3Ph+N)or208/220/230/240VAC(1Ph+N) |
3x360*/380*/400/415VAC(3Ph+N) |
|||
|
ACVoltageRegulation(Batt. Mode) |
± 1% |
||||
|
FrequencyRange(SynchronizedRange) |
46~54Hzor56~64Hz |
||||
|
FrequencyRange(Batt.Mode) |
50 Hz± 0.1Hz or60Hz ±0.1 Hz |
50/60 Hz ± 1% |
|||
|
CurrentCrestRatio |
3:1(max.) |
||||
|
HarmonicDistortion |
≦2%THD (Linear Load) ; ≦5 %THD (Non-linear Load) |
||||
|
TransferTime |
AC Modeto Batt.Mode |
Zero |
|||
|
InvertertoBypass |
Zero |
||||
|
Waveform(Batt.Mode) |
PureSinewave |
||||
|
OverloadCapability |
AC Mode |
100-110%for60min,111-125%for10min,126%~150%for1min;>150%immediatelyshutdown |
|||
|
BatteryMode |
|||||
|
BYPASS |
|||||
|
Nominal Voltage |
3x380/400/415VAC(3Ph+N) |
3x360/380/400/415VAC(3Ph+N) |
|||
|
VoltageRange |
-30% ~ +20% (Adjustable) |
305VAC~457VAC |
|||
|
FrequencyRange(SynchronizedRange) |
46~54Hzor56~64Hz |
46~54Hzor56~64Hz |
|||
|
OverloadCapability |
> 130% 1minute (default); continuouslyworking untilbreaker protection(optional) |
||||